Cable testing and insulation resistance (Megger) testing up to 33 kV
Vibhawa tests the insulation of LV and MV cables, switchgear, transformers, motors and solar PV arrays in Sri Lanka and the Maldives, from final circuits to 33 kV cables. Commonly known as a Megger test, though the technically correct term is insulation resistance testing, it shows whether a cable is safe to energise and whether its insulation is deteriorating. We test with our own calibrated instruments up to 5 kV DC, measure polarisation index (PI) and dielectric absorption ratio (DAR), carry out AC and DC high-voltage (hipot) testing on request, and every report is signed by a Chartered Electrical Engineer.

Megger test or insulation resistance test?
The same test. One is the name everyone uses on site; the other is the name in the standards.
What we test
Anything with insulation between a live conductor and earth, from a final circuit in an office to the 33 kV cable feeding a factory.
When to test
A cable that passed when it was laid can fail years later. These are the points where a test pays for itself.
Test voltages and pass values
The test voltage is set by the equipment's rated voltage. Readings are reported against the value that applies. Our guide What is a Megger test? explains each one.
| Equipment | DC test voltage | Acceptance |
|---|---|---|
| SELV and PELV circuits | 250 V | ≥ 0.5 MΩ (BS 7671) |
| LV circuits up to 500 V | 500 V | ≥ 1 MΩ (BS 7671) |
| Circuits above 500 V | 1,000 V | ≥ 1 MΩ (BS 7671) |
| Motors and generators | 500 V to 5 kV by rating | PI ≥ 2.0 and minimum IR (IEEE 43) |
| MV cables and switchgear, 11 kV and 33 kV | 5 kV | Manufacturer's or project specification; PI and trend |
These are minimums. A healthy new installation usually reads hundreds of megohms or more, and a value that has fallen since the last test matters more than the number on its own.
On site




How a cable testing job runs
Scope
Send the single-line diagram and cable schedule. We confirm what is tested, at what voltage, and how long the outage needs to be.
Isolate safely
Isolation, lock-off, proving dead and discharge under a safe system of work, with sensitive equipment disconnected first.
Test and record
Every core and circuit, with the test voltage, duration, temperature and humidity recorded so the next test can be compared.
Report
Results against acceptance values, PI and trends, failed circuits identified, and recommendations, signed by a Chartered Electrical Engineer.
Where we have done it
We have carried out insulation resistance and cable testing at hundreds of locations across Sri Lanka and the Maldives: factories, hotels and resorts, commercial towers, solar plants and utility-connected substations, from LV final circuits to 33 kV cables, switchgear and transformers.
Need only the instrument?
We hire calibrated LV and MV insulation resistance testers, with or without an engineer to run the test and write the report.
Related services
Frequently asked
If your question is not here, ask us. The scope call is free.
Is cable testing the same as a Megger test?
A Megger test, or more correctly an insulation resistance test, is the core of cable testing. For LV cables it is usually combined with continuity and polarity tests to BS 7671; for MV cables it is done at 5 kV DC with polarisation index, before energisation and periodically after.
What voltage do you use to test 11 kV and 33 kV cables?
Insulation resistance of MV cables is measured at 5 kV DC, each core against the other cores and the screen, unless the cable manufacturer or the project specification asks for something else.
Can you test a cable after a new joint or termination?
Yes. Testing after jointing and termination, and before the circuit is re-energised, is one of the most common requests we get.
How long does it take?
A spot reading on an LV circuit takes about a minute once it is isolated, and around fifty LV panels can be tested in a day. A polarisation index test takes ten minutes per test. We confirm the outage time when we scope the job.
Do you issue a test certificate?
You receive a test report with every result against its acceptance value, the instrument calibration certificates and the signature of a Chartered Electrical Engineer.
Do you do hipot (high-voltage withstand) testing?
Yes, on request. Where a specification or a manufacturer requires it, we carry out AC or DC hipot testing in addition to the insulation resistance test, with PI and DAR.
Do you test solar PV systems?
Yes. We test the insulation resistance of PV strings and DC cables to IEC 62446-1, and check string performance with our PV analysers, at commissioning and as periodic testing of rooftop and ground-mounted plants.
Do you work in the Maldives?
Yes, with our own engineers and instruments on site, under the same ISO 9001 processes as in Sri Lanka.
Cables to test before energisation, or due for a check?
Send the single-line diagram and cable schedule, and tell us the voltage and how long the outage can be. We will scope the tests and quote.